Plan Review Notes
Plan Review Notes For Permit 10060218
Permit Number 10060218
Review Stop B
Sequence Number 1
Notes
Date Text
2010-06-09 10:26:39****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE EXPLAIN THE "WIND INFORMATION" ON THE PLAN.
 THIS STATES THAT THIS IS AN INTERIOR RENOVATION, WHY IS
 THERE WIND INFORMATION ON THE PLAN?
  
 2. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 IMPROVEMENT. NO INFORMATION WAS PROVIDED, IS A PAGE
 MISSING?
  
 3. SHOW HOW EXITING IS AFFECTED, FBC10. DECLARE
 OCCUPANCY CLASSIFICATION FOR EACH AREA, AND SHOW HOW
 EXITING IS AFFECTED. IT APPEARS THAT YOU ARE CREATING A
 NEW EGRESS PATH, NOT CLEAR WHERE THE EXIT IS, OCCUPANT
 LOAD NOT STATED, HOW WILL THE ADDITIONAL OCCUPANTS
 WHICH MAY ELECT TO EXIT IN THIS DIRECTION AFFECT THE
 CURRENT EXITING CAPACITY? HOW WILL EXIT LIGHTING BE
 AFFECTED?
  
  
  