Plan Review Notes
Plan Review Notes For Permit 10060200
Permit Number 10060200
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-06-10 16:43:10*****DENIED*****
  
 1) USING THE PIPE SCHEDULE METHOD TO MODIFY AN EXISTING
 HYDRAULICALLY CALCULATED SYSTEM IS NOT PERMITTED BY
 NFPA 13.
  
 2) WHEN SYSTEM PRESSURE EXCEEDS 100 PSI, PROVIDE
 HANGERS THAT PREVENT UPWARD MOVEMENT FOR END OF LINE
 PENDENT SPRINKLERS OR ARMOVERS EXCEEDING 12" IN LENGTH.
  
 3) PROVIDE ADDRESS AND SUITE NUMBER (IF APPLICABLE) IN
 TITLEBLOCK.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
 561-805-6722