| Notes |
| Date |
Text |
| 2010-06-10 16:43:10 | *****DENIED***** | | | | | | 1) USING THE PIPE SCHEDULE METHOD TO MODIFY AN EXISTING | | | HYDRAULICALLY CALCULATED SYSTEM IS NOT PERMITTED BY | | | NFPA 13. | | | | | | 2) WHEN SYSTEM PRESSURE EXCEEDS 100 PSI, PROVIDE | | | HANGERS THAT PREVENT UPWARD MOVEMENT FOR END OF LINE | | | PENDENT SPRINKLERS OR ARMOVERS EXCEEDING 12" IN LENGTH. | | | | | | 3) PROVIDE ADDRESS AND SUITE NUMBER (IF APPLICABLE) IN | | | TITLEBLOCK. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 | | | 561-805-6722 |
|