| Plan Review Notes For Permit 10060179 |
| Permit Number |
10060179 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-08-12 12:51:45 | CARDINAL NEWMAN HIGH SCHOOL | | | 512 SPENCER DRIVE | | | PERMIT NUMBER 10060179 | | | | | | | | | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM INSTALLATION OR REMODELING. | | | | | | 2. NEW 3 HOUR FIRE SHUTTER IS TO BE DROP TESTED TO | | | ENSURE PROPER OPERATION AFTER INSTALLATION. ADDITIONAL | | | FUSIBLE LINKS WILL BE NEEDED TO TEST THE DOOR. THE TEST | | | OF THE DOOR SHALL BE WITNESSED BY A REPRESENTATIVE OF | | | THE BUREAU OF FIRE PREVENTION. | | | | | | | | | APPROVED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|