Plan Review Notes
Plan Review Notes For Permit 10060173
Permit Number 10060173
Review Stop P
Sequence Number 1
Notes
Date Text
2010-06-23 12:44:08PLUMBING PLAN REVIEW #1
 DENIED:
  
 1. SHEETS A.0, A.3, P-1, P-2
 SHEET A.0 LISTS THE AREA AS 4,022 SQUARE FEET. SEPERATE
 FACILITIES WILL BE REQUIRED FOR EACH SEX.
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 EXCEPTIONS:
 1. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR
 DWELLING UNITS AND SLEEPING UNITS.
 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
 3. SEPARATE FACILITIES SHALL NOT BE REQUIRED IN
 BUSINESS AND MERCANTILE OCCUPANCIES WITH A TOTAL FLOOR
 AREA OF 3,000 SQUARE FEET (279 M2) OR LESS.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  