2010-06-24 15:28:39REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. AC2, WATER SOURCE HEAT PUMP SCHEDULE, FRESH AIR,
 STATES SEE CALCS. I WAS UNABLE TO LOCATE THE
 CALCULATIONS REFERENCED ON THE PLAN. PLEASE PROVIDE
 CALCULATIONS, FBC M 403.2.
  
 2. PROVIDE INFORMATION REGARDING EXHAUST FOR THE TOILET
 ROOM, FBC M TABLE 403.3.
  
 3. PLEASE INCLUDE THE SYMBOL R (ENCIRCLED) IN THE
 LEGEND. THIS SYMBOL IS SHOWN AT THE THREE RETURNS.
  