| Permit Number |
10060173 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-10 14:16:41 | *****DENIED***** | | | | | | | | | 1. THE FLOOR PLAN AS SHOWN ON SHEET A.2, MORE REFLECTS | | | THAT OF A BUSINESS OCCUPANCY RATHER THAN A MERCANTILE | | | OCCUPANCY AS INDICATED IN THE PROJECT DATA INFORMATION. | | | | | | 2. ONLY ONE FIRE EXTINGUISHER COULD BE LOCATED. PROVIDE | | | ADDITIONAL FIRE EXTINGUISHER(S) TO SATISFY THE 75' | | | TRAVEL DISTANCE. | | | | | | 3. SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | SPECIFY INTERIOR FLOOR MATERIAL IN TERMS OF CLASS I OR | | | CLASS II. | | | | | | 4. NO FIRE SPRINKLER HEAD LAYOUT FOR THE NEW FLOOR | | | SHOWN. WILL THE PROJECT'S SCOPE OF WORK HAVE CAUSE FOR | | | THESE DEVICES TO BE RELOCATED / REMODELED ? | | | | | | 5. ON PAGE 1 OF THE FLORIDA ENERGY EFFICIENCY CODE'S | | | PROJECT SUMMARY INFORMATION DOES NOT CORRELATE WITH THE | | | PLAN. FOR EXAMPLE, 1) THE NUMERICAL ADDRESS, 2) | | | OCCUPANCY TYPE, 3) TENANT SPACE NUMBER, 4) SQUARE | | | FOOTAGE OF THE PROJECT | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|