| 2010-06-15 12:20:34 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING |
| | |
| | 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE |
| | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A |
| | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD |
| | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR |
| | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING |
| | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN |
| | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| | POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS |
| | CAN BE DEMONSTRATED ON THE PLANS INDICATING THE |
| | WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT |
| | CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES |
| | ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN |
| | THE CALCULATIONS. |
| | |
| | 2} 13-415.1.AB.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. |
| | A. A CONTROL DEVICE SHALL BE INSTALLED THAT |
| | AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF |
| | ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH |
| | MULTISCENE CONTROL, IN THE FOLLOWING: |
| | 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| | LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| | CLASSROOMS). |
| | 2. CONFERENCE/MEETING ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | |
| | 3}220.14 (G) SHOW WINDOWS. SHOW WINDOWS SHALL BE |
| | CALCULATED INACCORDANCE WITH EITHER OF THE FOLLOWING: |
| | (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER |
| | PROVISIONS |
| | OF THIS SECTION |
| | (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW |
| | WINDOW |
| | **** LOCATE SAME ON THE PLAN AND IN THE PANEL SCHEDULE |
| | |