| 2010-06-10 12:43:36 | BUILDING PLAN REVIEW |
| | PERMIT: 10060173 |
| | ADD: 201 S NARCISSUS # 120 |
| | CONT: BEST INTERIOR CONSTRUCTION |
| | TEL: (561)640-3010 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A.3 INDICATES THE USE OF WOOD LAMINATE |
| | FLOORING. PLEASE PROVIDE DOCUMENTATION INDICATING |
| | COMPLIANCE WITH FBC-B 805.1 APPLICATION. COMBUSTIBLE |
| | MATERIALS INSTALLED ON OR EMBEDDED IN FLOORS OF |
| | BUILDINGS OF TYPE I OR II CONSTRUCTION SHALL COMPLY |
| | WITH SECTIONS 805.1.1 THROUGH 805.1.3. |
| | |
| | 2) SHEET A.4 PROVIDES ELEVATIONS FOR VARIOUS CEILINGS |
| | BUT NO ADDITIONAL INFORMATION IS PROVIDED FOR THE TYPE |
| | OF CEILING MATERIALS, FRAMING, AND OR HANGING |
| | MATERIALS. |
| | |
| | 3) PLANS DO NOT PROVIDE FOR WALL FINISHES, 803.1 |
| | GENERAL. INTERIOR WALL AND CEILING FINISHES SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR |
| | FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING |
| | CLASSES IN ACCORDANCE WITH THEIR FLAME SPREAD AND |
| | SMOKE-DEVELOPED INDEXES. |
| | |
| | 4) SHEET A.2 THE LIFE SAFETY PLAN DOES NOT INDICATE |
| | WHERE DISPLAYS RACKS OR OTHER ASSOCIATED SALES ITEMS |
| | ARE LOCATED WITHIN A MERCANTILE OCCUPANCY. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |