| 2010-06-10 10:05:35 | PLUMBING REVIEW #1 | | | DENIED | | | | | | SHEET 3.0P & 3.1P - THE ADA W.C. IN THE WOMENS RESTROOM | | | HAS NO VENT. | | | | | | SHEET 3.0P & 3.1P - A DRY VENT IS REQUIRED BETWEEN THE | | | OTHER 2 WATER CLOSETS (A URINAL IS NOT INCLUDED IN THE | | | DEFINITION OF A BATHROOM GROUP). THE ADA W.C. IN THE | | | WOMENS RESTROOM COULD BE CONNECTED TO THIS CURCIT VENT | | | GROUP. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|