| Plan Review Notes For Permit 10060144 |
| Permit Number |
10060144 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2010-09-07 09:18:53 | BUILDING PLAN REVIEW | | | PERMIT: 10060144 | | | ADD: 338 MURRAY RD | | | CONT: O/B BROOKS, JAMES | | | TEL: (561)685-4340 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISOS: | | | | | | 1) SHOP DRAWINGS WILL BE REQUIRED FOR BOTH TRUSSES AND | | | LINTELS, TRUSS DESIGN MAY VERY FROM THE REVIEWED | | | DRAWINGS SHEET 4 OF 5. THE UPLIFT LOADS, LATERAL AND | | | GRAVITY LOADS MAY VERY GREATLY THAT WILL EFFECT THE | | | BASIC DESIGN AS WELL AS LINTEL DESIGNS. CONTRACTOR / | | | OWNER-BUILDER IS PROCEEDING HIS OR HER OWN RISK. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC... | | | | | | 2) FLAT ROOF: | | | FL1654-R4 | | | POLYGLASS- MODIFIED BITUMEN ROOF SYSTEMS | | | APPENDIX1, PAGE 10 OF 33 | | | W-26 SYSTEM -60.0 PSF | | | ZONES 2 & 3 REQUIRE ENHANCED FASTENING | | | LIMITATION 5.6 DOES ALLOW ENHANCED FASTENING IN ZONES | | | 2&3 BY A QUALIFIED DESIGN PROFESSIONAL. | | | TO BE PROVIDED AT TIME OF ROOFING PERMIT APPLICATION. | | | | | | METAL ROOF: | | | FL 11698 | | | ENGLERT INC. | | | DESIGN UPLIFT OF -124 PSF. C-BUCK ENGINEERING PRODUCT | | | APPROVAL. | | | |
|