Plan Review Notes
Plan Review Notes For Permit 10060144
Permit Number 10060144
Review Stop B
Sequence Number 2
Notes
Date Text
2010-08-19 13:13:37BUILDING PLAN REVIEW
 PERMIT: 10060144
 ADD: 338 MURRAY RD
 CONT: O/B BROOKS, JAMES
 TEL: (561)685-4340
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 19/ 2010
 2ND REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE SIGNED AND SEALED SOILS REPORTS (2).
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 BUILDING PROVISOS:
  
 1) SHOP DRAWINGS WILL BE REQUIRED FOR BOTH TRUSSES AND
 LINTELS, TRUSS DESIGN MAY VERY FROM THE REVIEWED
 DRAWINGS SHEET 4 OF 5. THE UPLIFT LOADS, LATERAL AND
 GRAVITY LOADS MAY VERY GREATLY THAT WILL EFFECT THE
 BASIC DESIGN AS WELL AS LINTEL DESIGNS. CONTRACTOR /
 OWNER-BUILDER IS PROCEEDING HIS OR HER OWN RISK.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 2) FLAT ROOF:
 FL1654-R4
 POLYGLASS- MODIFIED BITUMEN ROOF SYSTEMS
 APPENDIX1, PAGE 10 OF 33
 W-26 SYSTEM -60.0 PSF
 ZONES 2 & 3 REQUIRE ENHANCED FASTENING
 LIMITATION 5.6 DOES ALLOW ENHANCED FASTENING IN ZONES
 2&3 BY A QUALIFIED DESIGN PROFESSIONAL.
 TO BE PROVIDED AT TIME OF ROOFING PERMIT APPLICATION.
  
 METAL ROOF:
 FL 11698
 ENGLERT INC.
 DESIGN UPLIFT OF -124 PSF. C-BUCK ENGINEERING PRODUCT
 APPROVAL.
  