Plan Review Notes
Plan Review Notes For Permit 10060144
Permit Number 10060144
Review Stop B
Sequence Number 1
Notes
Date Text
2010-06-29 16:49:55BUILDING PLAN REVIEW
 PERMIT: 10060144
 ADD: 338 MURRAY RD
 CONT: O/B BROOKS, JAMES
 TEL: (561)685-4340
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE SIGNED AND SEALED SOILS REPORTS (2).
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 2) SHEET 4 OF 5 TRUSS LAYOUT SHEET DOES NOT PROVIDE THE
 UPLIFT, LATERAL OR GRAVITY LOADS TO BE RESISTED.
 FBC-R802.1.6.5 TRUSS TO WALL CONNECTIONS. THE PLANS
 ONLY INDICATE A HETAL 20 WOULD THIS CONNECTION BE USED
 FOR GIRDER TO WALL CONNECTIONS AS WELL?
  
 3) SHEET 2 OF 5 INDICATES A ROOF PRESSURE SCHEDULE WITH
 ONLY ONE SET OF VALUES. IS THIS VALUE FOR THE 6:12 ROOF
 OR THE FLAT ROOF? WE WILL NEED THE POSITIVE AND
 NEGATIVE PRESSURES FOR BOTH. THE CHARTS TO USE WILL BE
 THE 10 SQ FT SINCE THIS IS FOR COMPONENTS AND CLADDING.
 FBC- TABLE R.301.2(2).
  
 4) PLANS FAIL TO INDICATE COMPLIANCE WITH SEPARATION
 BETWEEN THE GARAGE AND HABITABLE AREAS OF THE
 RESIDENCE.
 406.1.4 SEPARATION. SEPARATIONS SHALL COMPLY WITH THE
 FOLLOWING:
 1. THE PRIVATE GARAGE SHALL BE SEPARATED FROM THE
 DWELLING UNIT AND ITS ATTIC AREA BY MEANS OF A MINIMUM
 1/2-INCH (12.7 MM) GYPSUM BOARD APPLIED TO THE GARAGE
 SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL BE
 SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LESS
 THAN A 5/8-INCH TYPE X GYPSUM BOARD OR EQUIVALENT. DOOR
 OPENINGS BETWEEN A PRIVATE GARAGE AND THE DWELLING UNIT
 SHALL BE EQUIPPED WITH EITHER SOLID WOOD DOORS OR SOLID
 OR HONEYCOMB CORE STEEL DOORS NOT LESS THAN 13/8 INCHES
 (34.9 MM) THICK, OR DOORS IN COMPLIANCE WITH SECTION
 715.4.3. OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A
 ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING.
 2. DUCTS IN A PRIVATE GARAGE AND DUCTS PENETRATING THE
 WALLS OR CEILINGS SEPARATING THE DWELLING UNIT FROM THE
 GARAGE SHALL BE CONSTRUCTED OF A MINIMUM 0.019-INCH
 (0.48 MM) SHEET STEEL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE.
 3. A SEPARATION IS NOT REQUIRED BETWEEN A GROUP R-3 AND
 U CARPORT, PROVIDED THE CARPORT IS ENTIRELY OPEN ON TWO
 OR MORE SIDES AND THERE ARE NOT ENCLOSED AREAS ABOVE.
  
 5) SHEET 3 OF 5 INDICATES (3) 3INCH VERTICAL PLUMBING
 RISERS, ARE THEY TO BE BUILT OUTSIDE OF THE MASONRY
 WALL OR ARE THEY TO BE PLACED WITHIN THE MASONRY WALL?
 106.1.2 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 7A) PGT SERIES FD-750 OUTSWING ALUMINUM FRENCH DOORS
 NOA 07-0103.02 IS EXPIRED AS OF FEB. 24/ 2010
 7B) PGT SERIES PW-701 ALUMINUM FIXED WINDOWS NOA
 07-0418.06 IS EXPIRED FEB 19, 2009
 7C) ROOFING POLYGLASS FL COVER SHEET FL985-R1 SUBMITTED
 WITH ENGLERT METAL ROOFING REPORT AS BACK UP REPORT.
 PLEASE SUBMIT THE PROPER POLYGLASS REPORT CIRCLE WHICH
 SUB-SYSTEM TO BE INSTALLED.
 7D) ENGLERT METAL ROOF FL# 6558 PLEASE HIGHLIGHT
 (CIRCLE) WHICH SUB-SYSTEM TO BE INSTALLED DEPENDING ON
 SELECTION, IT MAY REQUIRE ENHANCED FASTENING.
 7E) ROOFING FLAT DECK- MAY REQUIRE A DIFFERENT REPORT
 FROM THE POLYGLASS DEPENDING ON SELECTION.
 7F) LINTELS- WITH THE NEW WALL HEIGHT OF 9???-4??? IT
 WOULD APPEAR A LINTEL WILL BE REQUIRED, PLEASE
 HIGHLIGHT (CIRCLE LINTEL TO BE INSTALLED.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NOTE OF CAUTION: PLANS INDICATE FUTURE POOL, THE
 FOOTERS FOR THE BACK PORCH MAY BE OF CONCERN WHEN THE
 POOL IS BEING DUG & INSTALLED PLEASE BE AWARE OF
 R403.1.7.2.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  