2010-10-08 11:36:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 2. PROVIDE STRUCTURAL INFORMATION TO SHOW HOW THIS WILL
 RESIST WIND LOADS, FBC1609. INFORMATION SUCH AS
 SUBSTRATE, FASTENERS, FASTENING PATTERN SHOULD BE
 INCLUDED.
  
 2ND REVIEW, AS DISCUSSED WITH CONTRACTOR, PLAN SHOULD
 INCLUDE MINIMUM INFORMATION SUCH AS FASTENER SIZE
 (DIAMETER, MINIMUM EMBEDMENT), FASTENING PATTERN (SUCH
 AS NUMBER PER SIDE).
  
 3. PROVIDE A PLAN WHICH SHOWS LOCATION OF PROPOSED
 SIGN, FBC106.
  
 2ND REVIEW, THE PHOTOGRAPH PROVIDED DOES NOT CLEARLY
 SHOW LOCATION. PROVIDE A PLAN (SUCH AS A COPY OF THE
 SURVEY OR PLAN OF THE BUILDING INCLUDING "NORTH") AND
 ON THE PLAN, SHOW WHERE THE SIGN IS PROPOSED. THE
 PHOTOGRAPH SHOWS TWO LOCATIONS, BUT ALL VERBAGE IS FOR
 "SIGN" (SINGULAR), SO SCOPE OF WORK PROPOSED IS NOT
 CLEAR FBC106.
  
 4. THE NAME AND SIGNATURE OF THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE STRUCTURAL DESIGN IS TO BE
 INCLUDED ON THE PLAN.
  
  