| Plan Review Notes For Permit 10060137 |
| Permit Number |
10060137 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-24 15:47:00 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | PROVIDE VENTILATION CALCULATIONS FOR ALL RECONFIGURED | | | SPACES WITHIN THE WORK AREA IN ACCORDANCE WITH FBC-EB | | | 709.1 AND FBC-M 403.3. INCLUDE SPACE-BY-SPACE | | | CALCULATIONS FOR OCCUPANCY CLASSIFICATION, OCCUPANT | | | LOAD AND VENTILATION RATES IN ACCORDANCE WITH FBC-M | | | TABLE 403.3. | | | | | | NOTE: COMMERCIAL KITCHEN EXHAUST/VENTILATION SYSTEM IS | | | NOT PART OF THE SCOPE FOR THIS REVIEW. SEPARATE PLANS | | | AND PERMIT APPLICATIONS ARE REQUIRED FOR HOOD SYSTEMS, | | | SUPPRESSION SYSTEMS AND WALK-IN COOLERS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|