| Plan Review Notes For Permit 10060137 |
| Permit Number |
10060137 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-24 12:33:18 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING | | | | | | 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE | | | 13-415.1AB.1.1 FOR TIME CLOCK REQUIREMENTS. ALL THAT IS | | | REQUIRED FOR THE ELECTRICAL REVIEW IS THE BASIC | | | PRESCRIPTIVE REQUIREMENTS. SEE 13-415.2.AB.5 INTERIOR | | | LIGHTING POWER, SCOPE. | | | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR | | | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING | | | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD | | | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE | | | METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED | | | INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH | | | SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR | | | LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH | | | SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE | | | DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF | | | THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE | | | DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE | | | SCHEDULE TO CORRELATE WITH THE ONES IN THE | | | CALCULATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|