| 2010-06-10 09:53:19 | BUILDING PLAN REVIEW |
| | PERMIT: 10060137 |
| | ADD: 1100 S DIXIE HWY |
| | CONT: TO BE DETERMINED ( RYCON) |
| | TEL: (412)287-9961 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NO PERMIT APPLICATION, PLANS SUBMITTED WITH ONLY A |
| | PLAN/ PERMIT REVISION AND SUBMITTAL FORM. 105.1 THE |
| | CONTRACTOR SHALL FIRST MAKE APPLICATION TO THE BUILDING |
| | OFFICIAL AND OBTAIN THE REQUIRED PERMIT BEFORE THE |
| | START OF WORK. |
| | |
| | 2) G002- REFERENECES THE CONSTRUCTION TYPE AS A TYPE |
| | IIB. THE BUILDING WAS ORIGINALLY BUILT UNDER THE 94 SBC |
| | AAND BUILDING TYPE II WHICH TRANSLATES INTO THE 2007 |
| | FBC-B AS A BUIULDING TYPE I-B PLEASE UPDATE PLANS. |
| | |
| | 3) G002 - CODE PLEASE UPDATE THE PLANS TO THE 2007 |
| | FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS, & 2007 |
| | FLORIDA EXISTING BUILDING CODE W/ 2009 SUPPLEMENTS. |
| | FL EXT BLDG CODE SECTION 401.4 A DESIGN PROFESSIONAL OR |
| | AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF |
| | THIS CODE. |
| | |
| | 4) G-002 FIRE RESISTANCE RATINGS REFRENENCE THE 2006 |
| | IBC TABLE 600, PLEASE UPDATE TO THE FLORIDA CODES AND |
| | CORRECT SECTIONAND OR TABLE. |
| | |
| | 5) SHEETS D100 & A100, ON THE INTERIOR DEMO PLAN NOTE |
| | #8 INDICATES THE ELIMINATION OF A SECURITY GRILLE BUT |
| | ON SHEET A100 THERE IS NO MENTION OF WALL TYPE |
| | CONFIGURATION AND OR IF THE WALL IS A RATED WALL? THIS |
| | WOULD APPEAR TO BE A SEPERATE TENANT WITH A CHICK-FIL-A |
| | FRANCHISE OCCUPYING THIS SPACE.FBC-B 708.1(7). |
| | |
| | 6) PLEASE PROVIDE A COMPLETE PLAN OF THE PROPOSED |
| | TENANT SPACE. IT APPEARS FROM THE ORIGINAL PERMITED |
| | BUILDING PLANS ( 96012215): |
| | |
| | 6A) THE TENANT SPACE HAS INCREASED INTO THE COMMON AREA |
| | OR RECEIVING AREA ? |
| | |
| | 6B) PLANS ARE NOT CLEAR WITHIN THE RECEIVING AREA IF |
| | THE OVERHEAD GRILLE IS STILL THERE? OR REMOVED AND NEW |
| | WALL SYSTEM IS CURRENTLY IN PLACE OR WILL BE INSTALLED |
| | AS NEW WORK UNDER THIS PERMIT? |
| | |
| | 6C) IF THE OVERHEAD GRILLE IS EXISTING AND NOT TO BE |
| | REMOVED, THEN THIS AREA WOULD BE CONSIDERED EXTERIOR OR |
| | REQUIRING PRODUCT APPROVALS FOR THE NEW WALK-IN |
| | COOLERS. RULE 9B-72 (31)(G) EXTERIOR WALK-IN COOLERS & |
| | FREEZERS. WILL NEED TO INDICATE COMPLIANCE WITH WIND |
| | PRESSURES AND ANCHORAGE FOR 140 MPH, COASTAL EXPOSURE, |
| | NOTE HEIGHT ADJUSTMENT FACTORS FOR BUILDING HEIGHT. |
| | |
| | 6D) PLEASE PROVIDE A NEW LS PLAN FOR THE EXSPANDED |
| | TENANT SPACE, 106.3.5.(7) / 1015.2.1 EXCEP(2) IT |
| | APPEARS THE OVER ALL DIAGONAL OF THE TENANT SPACE (WITH |
| | RECEIVING AREA INCLUDED) & WITH FIRE SPRINKLERS THE TWO |
| | EXIT ACCESS DOORWAYS APPEAR TO BE LESS THAN 1/3 THE |
| | OVERALL DIAGONAL APART. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |