| Plan Review Notes For Permit 10060133 |
| Permit Number |
10060133 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-16 15:53:12 | *****DENIED***** | | | | | | 1) PROVIDE CHECK VALVE IN FEED MAIN FROM FIRE | | | DEPARTMENT CONNECTION. | | | | | | 2) PROVIDE DETAIL OF FIRE DEPARTMENT CONNECTION. | | | | | | 3) FLUSH THE FIRE MAINS PER NFPA 24. | | | | | | 4) DOCK "B" IS NOT REFERENCED ANYWHERE ON SHEET C-4. | | | | | | 5) PROVIDE NUMERICAL ADDRESS OF JOB IN THE TITLEBLOCK. | | | | | | 6) PROVIDE ONLY SHEETS PERTINENT TO FIRE PROTECTION; | | | IRRIGATION PLANS ETC. NOT WANTED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | 561-805-6730 | | | |
|