2010-06-16 15:53:12*****DENIED*****
  
 1) PROVIDE CHECK VALVE IN FEED MAIN FROM FIRE
 DEPARTMENT CONNECTION.
  
 2) PROVIDE DETAIL OF FIRE DEPARTMENT CONNECTION.
  
 3) FLUSH THE FIRE MAINS PER NFPA 24.
  
 4) DOCK "B" IS NOT REFERENCED ANYWHERE ON SHEET C-4.
  
 5) PROVIDE NUMERICAL ADDRESS OF JOB IN THE TITLEBLOCK.
  
 6) PROVIDE ONLY SHEETS PERTINENT TO FIRE PROTECTION;
 IRRIGATION PLANS ETC. NOT WANTED.
  
  
  