2010-06-21 10:04:25****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. EXPOSURE CATEGORY C DESIGN PRESSURES REQUIRED.
 FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE CHANGED
 EFFECTIVE MARCH 1, 2009. PRESSUES SUBMITTED ARE TOO LOW
 BUT ANCHOR SPACING APPEARS TO BE COMPLIANT.
  
 2. SHUTTER MOUNTING CONNECTION TYPE WAS NOT COMPLETED
 ON THE INSTALLATION SCHEDULE. PLEASE SEE PAGE 11 OF THE
 PRODUCT APPROVAL. IF C1 OR C2 ARE USED, 12" SPACING
 COMPLIES. IF ANOTHER MOUNTING TYPE IS USED, REVISION
 REQUIRED.
  
  
  
  
  