| 2010-06-24 13:36:48 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- ROOF SHEATHING UPLIFT AND ROOF-TO-WALL UPLIFT LOADS |
| | SHALL BE INCREASED BY 20 PERCENT AS REQUIRED BY SEC. |
| | R301.2.1.4.3(2). REVISE STRUCTURAL DRAWINGS AS REQUIRED |
| | TO COMPLY WITH THIS SECTION. |
| | |
| | 3- SPECIFY THE DESIGN PRESSURES CALCULATED FOR THE |
| | DOORS AND WINDOWS TO VERIFY COMPLIANCE WITH SEC. R301. |
| | |
| | 4- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | COOKING EQUIPMENT SHOWING THAT THE EQUIPMENT WAS |
| | DESIGNED TO BE INSTALLED ON THE PORCH A SHOWN ON PLANS. |
| | |
| | 5- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR NEW |
| | FIREPLACE TO BE INSTALLED ON THE NEW PAVILION TO SHOW |
| | COMPLIANCE WITH CHAPTER 10 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 6- TIMBER STRUCTURAL DRAWINGS AND CALCULATIONS |
| | SUBMITTED: |
| | A) REVISE DESIGN CRITERIA TO COMPLY WITH THE 20% |
| | INCREASED LOADS AS REQUIRED BY SEC. R301.2.1.4.3(2). |
| | SEE ITEM # 2 ABOVE. |
| | |
| | B) REVISE DESIGN CRITERIA. EXPOSURE "D" IS NOT |
| | APPLICABLE IN FLORIDA. SEE SEC. R301.2.1.4.3(3). |
| | |
| | C) ENGINEER (THOMAS R. BEAUDETTE) NEED TO USE CURRENT |
| | FLORIDA ENGINEER'S SEAL. ENGINEER'S SEAL NEED TO SAY |
| | "LICENSE" NOT "CERTIFICATE. THE SEAL WAS TO BE UTILIZED |
| | PRIOR TO JANUARY 1, 2002. SEE SEC. 61G15-23.001 OF |
| | FLORIDA ADMINISTRATIVE CODE AND SEC. 471.025 OF FLORIDA |
| | STATUTE. |
| | |
| | D) ENGINEER OF RECORD (ALBERT A. GARGIULO) TO REVIEW |
| | AND APPROVE ALL TIMBER DRAWINGS PRIOR TO SUBMITTAL TO |
| | THIS OFFICE. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY |
| | SPECIFY MULLION SIZE AND FASTENERS TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES REQUIRED BY SEC. R301. |
| | |
| | B) GLASS BLOCK AS SHOWN ON PLANS. |
| | |
| | C) PRECAST LINTELS AS SHOWN ON PLANS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 9- OWES $19.74 FOR RADON FEES AND LANDSCAPE REVIEW FEE. |
| | |
| | 10- SHEET A-2: REVISE TOP OF CHIMNEY CAP ELEVATION |
| | SHOWN ON PARTIAL SOUTH ELEVATION. IT CAN'T BE 8'-2". |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |