| Plan Review Notes For Permit 10060009 |
| Permit Number |
10060009 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-03 12:26:56 | *****DENIED***** | | | | | | 1) DEVICE LABELED AS "SECURITY HORN" SHOULD BE LABELED | | | A FIRE ALARM SPEAKER PER NFPA 72. | | | | | | 2) VERIFY DEVICE LABELED AS SECURITY KEY PAD DOES NOT | | | RESTRICT EXIT ACCESS FOR TENANTS. | | | | | | 3) NORTHEAST CORRIDOR ON FLOOR PLAN SHOWS A WALL | | | CLOSING OFF THE CORRIDOR. THIS WALL DOES | | | NOT MATCH THE ARCHITECTURAL FLOOR PLAN. | | | | | | 4) PLEASE EXPLAIN THE BLANK "ENGINEER" BOX LOCATED IN | | | THE TITLEBLOCK. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|