| Plan Review Notes For Permit 10050766 |
| Permit Number |
10050766 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-03 09:40:29 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | | AT | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL | | | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE | | | INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609, | | | FBC*106. SCOPE OF WORK NOT CLEAR, PLANS STATE THAT | | | SHUTTERS ARE EXISTING BUT A PRODUCT APPROVAL WAS | | | PROVIDED AND NO RECORD OF EXISTING SHUTTERS. | | | | | | 3. PROVIDE A DETAIL FOR THE DECORATIVE SHUTTERS, FBC | | | R301, SHOWING HOW THEY WILL RESIST WIND LOADS. | | | | | | 4. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR | | | EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE | | | CHANGED EFFECTIVE MARCH 1, 2009. THIS PROJECT IS WITHIN | | | THE 1500 FOOT TRANSITION ZONE. | | | | | | 5. A ROOF PERMIT WILL BE REQUIRED. | | | | | | 6. PROVIDE PRODUCT APPROVAL FOR THE PROPOSED ROOF. | | | |
|