2010-06-03 09:40:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106. SCOPE OF WORK NOT CLEAR, PLANS STATE THAT
 SHUTTERS ARE EXISTING BUT A PRODUCT APPROVAL WAS
 PROVIDED AND NO RECORD OF EXISTING SHUTTERS.
  
 3. PROVIDE A DETAIL FOR THE DECORATIVE SHUTTERS, FBC
 R301, SHOWING HOW THEY WILL RESIST WIND LOADS.
  
 4. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR
 EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE
 CHANGED EFFECTIVE MARCH 1, 2009. THIS PROJECT IS WITHIN
 THE 1500 FOOT TRANSITION ZONE.
  
 5. A ROOF PERMIT WILL BE REQUIRED.
  
 6. PROVIDE PRODUCT APPROVAL FOR THE PROPOSED ROOF.
  