| Plan Review Notes For Permit 10050764 |
| Permit Number |
10050764 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-28 15:29:10 | *****DENIED***** | | | | | | | | | 1) PROVIDE HYDRAULIC CALCULATIONS AS ADDITIONAL | | | SPRINKLERS HAVE BEEN ADDED TO EXISTING BRANCH LINES. | | | | | | 2) 2-1/2" CROSS MAIN SIZE CONFLICTS WITH ORIGINAL 2007 | | | DRAWINGS SHOWING 2" CROSS MAINS. | | | | | | 3) DRAWING SCALE IS 1/8"=1'-0" NOT 1/4"=1'-0". | | | | | | | | | WESLEY JOLIN & | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6730 |
|