| Plan Review Notes For Permit 10050763 |
| Permit Number |
10050763 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-06-07 13:25:56 | *****APPROVED W/PROVISO***** | | | | | | AFTER CONFERRING WITH THE FIRE ALARM CONTRACTOR, PLAN | | | SHEET FA-1 WAS STAMPED, INITIALED, AND DATED; READY FOR | | | PERMIT ISSUANCE. IT WAS UNDERSTOOD OF THE FOLLOWING | | | PROVISO FOR THE ISSUANCE OF THIS PERMIT: | | | | | | PRIOR TO THE FIRE ALARM FINAL - INSPECTION CODE #302, | | | REVISED PLANS (SHOWING THE ADDED DUCT DETECTOR'S | | | ADDRESS AND SHOWING HOW IT IS ADDED TO THE FIRE ALARM | | | RISER DIAGRAM) SHALL BE SUBMITTED TO THIS OFFICE FOR | | | REVIEW, APPROVAL, AND RETENTION. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|