2010-06-08 16:49:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE AN
 EMERGENCY ESCAPE AND RESCUE OPENING FOR EACH BEDROOM.
 FBC EXISTING BUILDING 604.
  
 2. FBC R310, FBC EB 604.1, EMERGENCY ESCAPE AND RESCUE
 FOR SLEEPING ROOMS, PROVIDE THE CLEAR OPENING SIZE FOR
 EACH EMERGENCY ESCAPE AND RESCUE WINDOW (WIDTH, HEIGHT,
 TOTAL CLEAR OPENING SF AREA). THE CLEAR OPENING CANNOT
 BE REDUCED BY MORE THAN 5%. SINGLE HUNG WINDOWS WHICH
 COMPLIED WITH THE CODE IN EFFECT AT THE TIME OF
 INSTALLATION WERE INSTALLED, AND IT APPEARS THAT NON
 COMPLIANT WINDOWS ARE PROPOSED. FOR INSTANCE, MASTER
 BEDROOM HAS A 35"X49" SINGLE HUNG WINDOW INSTALLED. A
 HORIZONTAL ROLLER WINDOW WOULD HAVE A WIDTH OF
 APPROXIMATELY 16" (20" REQUIRED).
  
  