| Notes |
| Date |
Text |
| 2010-06-22 13:49:56 | 2007 FBC W/2009 REVISIONS | | | | | | A) MAIN HOUSE | | | | | | MECHANICAL DENIED | | | | | | 1) SUBMIT 2 COPIES OF THE HVAC PLAN. PLANS ARE REQUIRED | | | TO BE A MINIMUM OF 1/8" SCALE. THE PLANS THAT WERE | | | SUBMITTED ARE TOO SMALL. CITY AMENDMENTS 106.1.3 | | | | | | 2) FBC R M1602.2 DOES NOT ALLOW RETURN AIR TO BE TAKEN | | | FROM THE KITCHEN. PLEASE REVISE PLANS. | | | | | | | | | B) GARAGE/APARTMENT | | | | | | NO MECHANICAL PLANS OR CALCULATIONS WERE SUBMITTED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|