| 2010-06-23 14:18:37 | 2007 FBC W/2009 REVISIONS |
| | |
| | A) MAIN HOUSE |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |
| | 2) THE EXPOSURE CATEGORY IS INCORRECTLY SPECIFIED ON |
| | THE PLANS AS EXPOSURE B AND IT SHOULD BE C. PLEASE |
| | CORRECT AND ADJUST THE CORRESPONDING WIND-LOAD |
| | PRESSURES ACCORDINGLY. SEE FBC R 301.2.1.4.3. |
| | |
| | 3) THE ENERGY CALC. FORM IS REQUIRED TO BE SIGNED BY |
| | THE OWNER/AGENT. THE INSULATION R VALUES LISTED ON THE |
| | FORM DO NOT MATCH THE ONES SPECIFIED ON THE WALL |
| | SECTION ON SHEET 3 OF THE PLANS. PLEASE CORRECT. |
| | |
| | 4) THE MASONRY FOUNDATION STEM WALLS ARE REQUIRED TO |
| | HAVE VERTICAL REINFORCEMENT PER FBC R404.1.1. SPECIFY |
| | THE SIZE AND SPACING OF THE VERTICAL REINFORCING. |
| | |
| | 5) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE ROOF |
| | SHINGLES, TRUSS CONNECTORS AND STRAPS AS REQUIRED BY |
| | DCA RULE 9B-72. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R807.1 FOR ATTIC ACCESS. |
| | |
| | |
| | |
| | B) NEW GARAGE/ APARTMENT |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A SEPARATE APPLICATION WITH SEPARATE PERMIT NUMBERS |
| | WILL BE REQUIRED FOR THE GARAGE / APARTMENT. |
| | |
| | 2) THE GARAGE APARTMENT WILL BE REQUIRED TO HAVE AN |
| | ADDRESS FOR THE BUILDING. CONTACT JOHN NGUYEN AT (561) |
| | 822-1239. |
| | |
| | 3) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 |
| | |
| | 4) SUBMIT 2 SETS OF ENERGY CALCULATIONS FOR THE GARAGE |
| | APARTMENT. |
| | |
| | 5) THE EXPOSURE CATEGORY IS INCORRECTLY SPECIFIED ON |
| | THE PLANS AS EXPOSURE B AND IT SHOULD BE C. PLEASE |
| | CORRECT AND ADJUST THE CORRESPONDING WIND-LOAD |
| | PRESSURES ACCORDINGLY. SEE FBC R 301.2.1.4.3. |
| | |
| | 6) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS |
| | REQUIRED BY FBC R807.1. |
| | |
| | 7) SPECIFY THE SIZE AND SPACING OF THE FLOOR JOISTS AT |
| | THE WOOD DECK. |
| | |
| | 8) THE SIMPSON LCB44 SPECIFIED ON SHEET E1 AT THE BASE |
| | OF THE 6 X 6 POSTS IS FOR 4 X 4 POSTS. THE LCB66 IS FOR |
| | 6 X 6 POSTS. |
| | |
| | 9) SHOW THAT STAIRS COMPLY WITH FBC R 311.5.1 FOR 36" |
| | MINIMUM CLEAR WIDTH. |
| | |
| | 10) SHOW COMPLIANCE WITH FBC R 311.5.6.1 THROUGH |
| | 311.5.6.3 FOR HANDRAIL REQUIREMENTS AT THE EXTERIOR |
| | STAIRS. |
| | |
| | 11) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE ROOF |
| | COVERING, SLIDING GLASS DOOR, EXTERIOR OUTSWING DOORS, |
| | SECTIONAL GARAGE DOOR AS REQUIRED BY DCA RULE 9B-72. |
| | |
| | 12) SHOW COMPLIANCE WITH FBC R309.2 GARAGES BENEATH |
| | HABITABLE ROOMS SHALL BE SEPARATED BY NOT LESS THAN |
| | 5/8-INCH TYPE X GYPSUM BOARD OR EQUIVALENT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |