| Plan Review Notes For Permit 10050628 |
| Permit Number |
10050628 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-07 09:12:01 | PLANS DENIED | | | 1) PLEASE SHOW THE MOTORIZED DAMPER IN THE RETURN AIR | | | DUCT ON THE PLANS . | | | 2) PLEASE PROVIDE THE LOCATION OF THE PACKAGE UNIT ON | | | THE ROOF OR GROUND ON THE PLANS. | | | 3) PLEASE REFER TO SECTION 606.2.1 FBC (M) 2007 SUPPLY | | | AIR | | | 4) SEPARATE PERMITS ARE REQUIRED FOR THE WALK IN COOLER | | | OR FREEZER | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|