| Plan Review Notes For Permit 10050628 |
| Permit Number |
10050628 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-08 16:49:58 | *****DENIED***** | | | | | | | | | 1. THE ADDRESS NUMBER LISTED IN THE TITLE BLOCK OF THE | | | PLANS (6405) DOES NOT CORRELATE WITH THE ADDRESS NUMBER | | | (6505) LISTED ON THE PERMIT APPLICATION. THE ACTUAL | | | PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF | | | EACH SUBMITTED PLAN SHEET. | | | | | | 2. WHAT WAS THE PREVIOUS OCCUPANCY TYPE? | | | | | | 3. THE PERMIT APPLICATION INDICATES THAT THE PROJECT | | | SCOPE OF WORK WILL BE IN SUITE 101 WHICH ENTAILS THAT | | | THERE ARE ADDITIONAL TENANT SPACES UNDER THE BUILDING | | | ADDRESS OF 6505 SOUTH DIXIE HIGHWAY. PLEASE VERIFY AND | | | ADVISE. | | | | | | 4. SPECIFY THE INTERIOR FINISH FOR WALLS AND CEILING IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5. ON SHEET 6.1, THE 2003 EDITION OF NFPA 101 IS | | | INCORRECTLY REFERENCED. THIS SHOULD BE THE 2006 EDITION | | | AS CORRECTLY LISTED ON 1.1 SHEET. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|