2010-07-28 08:41:06BUILDING REVISION APPROVED WITH PROVISO:
  
 1- REVISE DESIGN PRESSURES ON SHEET S-1. DESIGN
 PRESSURES SHOWN ON THE 2 STORY SKETCH DON'T MATCH THE
 DESIGN PRESSURES SHOWN UNDER THE TWO STORY WORST CASE
 SCENARIO AND UNDER THE WIND PRESSURES SHOWN FOR THE TWO
 STORY EDGE AND INTERIOR ZONES. SEE COMMENTS ON SHEET
 S-1 SUBMITTED.
  
 2- A) PROVIDE COMPLETE SPECIFICATIONS FOR ELEVATOR TO
 BE INSTALLED.
  
 B) DESIGNER OF RECORD TO REVIEW AND APPROVE SPECS
 PACKAGE PRIOR TO SUBMITTAL.
  
  
  
 ***REMAINDER: PROVIDE INFORMATION REQUESTED ON PROVISO
 DATED 7/01/10. SEE COPY BELOW.
  
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF TILE ADHESIVE. TITESET ROOFING ADHESIVE
 SUBMITTED IS NOT LISTED ON THE ROOF TILE NOA. NEED TO
 SHOW WHAT'S THE MIN. ATTACHMENT RESISTANCE TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
  
 B) SEALOFLEX WATERPROOFING NOA 05-0901.04: ENGINEER
 NEEDS TO REVISE THE RAS 117 CALCULATIONS. THE MIN.
 FASTENER SEPARATION SHALL NOT BE LESS THAN 4"O.C. SEE
 SEC. 8.1 OF RAS 117.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 105.3.3 CITY AMENDMENTS TO
 FBC. THIS APPLIES TO PRODUCT APPROVALS THAT NEED TO BE
 RE-SUBMITTED.
  
 3- SHEET S1: REVISE DESIGN PRESSURES FOR WALL OPENINGS
 IN EXPOSURE "C". REVISE SKETCH FOR ONE STORY ALSO AND
 COORDINATE WITH DESIGN PRESSURES SHOWN AT BOTTOM OF
 PAGE.