| Notes |
| Date |
Text |
| 2010-07-01 15:45:26 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) ROOF TILE ADHESIVE. TITESET ROOFING ADHESIVE | | | SUBMITTED IS NOT LISTED ON THE ROOF TILE NOA. NEED TO | | | SHOW WHAT'S THE MIN. ATTACHMENT RESISTANCE TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301. | | | | | | B) SEALOFLEX WATERPROOFING NOA 05-0901.04: ENGINEER | | | NEEDS TO REVISE THE RAS 117 CALCULATIONS. THE MIN. | | | FASTENER SEPARATION SHALL NOT BE LESS THAN 4"O.C. SEE | | | SEC. 8.1 OF RAS 117. | | | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS. SEC. 105.3.3 CITY AMENDMENTS TO | | | FBC. THIS APPLIES TO PRODUCT APPROVALS THAT NEED TO BE | | | RE-SUBMITTED. | | | | | | 3- SHEET S1: REVISE DESIGN PRESSURES FOR WALL OPENINGS | | | IN EXPOSURE "C". REVISE SKETCH FOR ONE STORY ALSO AND | | | COORDINATE WITH DESIGN PRESSURES SHOWN AT BOTTOM OF | | | PAGE. |
|