| Plan Review Notes For Permit 10050571 |
| Permit Number |
10050571 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-08 17:12:07 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- DRAWING M1 NEEDS TO BE SIGNED AND SEALED BY THE | | | ARCHITECT AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE. | | | | | | 2- CFM'S CALCULATED ON THE MANUAL J CALCULATIONS AND | | | CFM'S SPECIFIED ON DRAWING M1 DON'T MATCH. REVISE AS | | | REQUIRED TO MATCH. | | | | | | 3- CONDENSING UNIT MOUNTING DETAIL INFORMATION IS NOT | | | CLEAR AND REVISE CITED CODE SECTION. CLEARLY SPECIFY | | | STRAPS SIZE AND FASTENERS SIZE (DIAMETER AND LENGTH) TO | | | BE USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES | | | OF SEC. R301. AND, CORRECT CODE SECTION TO USE IS SEC. | | | M1307.3. SEE 2007 FLORIDA RESIDENTIAL CODE AND REVISE | | | AS REQUIRED. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|