2010-06-08 17:12:07RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- DRAWING M1 NEEDS TO BE SIGNED AND SEALED BY THE
 ARCHITECT AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- CFM'S CALCULATED ON THE MANUAL J CALCULATIONS AND
 CFM'S SPECIFIED ON DRAWING M1 DON'T MATCH. REVISE AS
 REQUIRED TO MATCH.
  
 3- CONDENSING UNIT MOUNTING DETAIL INFORMATION IS NOT
 CLEAR AND REVISE CITED CODE SECTION. CLEARLY SPECIFY
 STRAPS SIZE AND FASTENERS SIZE (DIAMETER AND LENGTH) TO
 BE USED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF SEC. R301. AND, CORRECT CODE SECTION TO USE IS SEC.
 M1307.3. SEE 2007 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER