| 2010-09-13 14:12:54 | 2004 FBC | | | REVISION | | | SHEET P2 | | | | | | GAS REVIEW | | | REVISION REQUIRED | | | | | | ON SHEET P-2.0, THE TOTAL DEVELOPED GAS PIPE LENGTH | | | FROM METER TO FURTHEST APPLIANCE IS 165' - 9" NOT 127' | | | - 1" AND THE TOTAL LENGTH OF ALL PIPING IS 228' - 6" | | | NOT 189' - 9". THESE DIFFERENCES REQUIRE 1-1/2" PIPE | | | FROM THE METER TO THE FIRST BRANCH AND 1 - 1/4" PIPE | | | FROM FIRST BRANCH TO THE SECOND BRANCH. SEE REDLINES ON | | | DENIED PLANS. SUBMIT A SEPARATE GAS PERMIT WITH TWO | | | SETS OF REVISED GAS ISOMETRIC DRAWINGS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|