Plan Review Notes
Plan Review Notes For Permit 10050503
Permit Number 10050503
Review Stop B
Sequence Number 1
Notes
Date Text
2010-05-18 15:15:45RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- SPECIFY WHICH APPROVED ASSEMBLY AND WHICH BASE SHEET
 FASTENING OPTION FROM NOA 09-0224.01 SUBMITTED IS GOING
 TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
 ***NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL
 LIMITATION #9 ARE NOT ALLOWED TO BE USED IN THIS AREA
 BECAUSE THEY DON'T MEET THE DESIGN PRESSURES OF SEC.
 R301.
  
 2- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C". SEC. R301.2.1.4.3 OF 2009
 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  