| Plan Review Notes For Permit 10050503 |
| Permit Number |
10050503 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-18 15:15:45 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- SPECIFY WHICH APPROVED ASSEMBLY AND WHICH BASE SHEET | | | FASTENING OPTION FROM NOA 09-0224.01 SUBMITTED IS GOING | | | TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | ***NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL | | | LIMITATION #9 ARE NOT ALLOWED TO BE USED IN THIS AREA | | | BECAUSE THEY DON'T MEET THE DESIGN PRESSURES OF SEC. | | | R301. | | | | | | 2- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS | | | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. | | | | | | B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | | TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS | | | LOCATED ON EXPOSURE "C". SEC. R301.2.1.4.3 OF 2009 | | | REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|