| 2010-05-20 15:07:44 | FBC PLUMBING 2007 | | | REVIEW #1 | | | DENIED: | | | | | | 1. WATER CLOSETS IN ROOMS 204 B & 205 B HAVE NO VENT. | | | FBC PLUMBING 901.2.1 VENTING REQUIRED. | | | EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED ... | | | | | | 2. VENT FOR W.C. IN 204 A IS A HORIZONTAL DRY VENT. | | | 905.3 VENT CONNECTION TO DRAINAGE SYSTEM. | | | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL | | | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN | | | PIPE.905.4 VERTICAL RISE OF VENT. | | | EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 | | | INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE | | | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|