| Plan Review Notes For Permit 10050399 |
| Permit Number |
10050399 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-27 16:16:24 | BUILDING PLAN REVIEW | | | PERMIT: 10050399 | | | ADD: 1200 S FLAGLER PH# 5 | | | CONT: THE ELITE COMPANIES | | | | | | TEL: (561)262-1175 | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THE DRAWING SUPPLIED BY THE WIELDER ENGINEERING FIRM | | | WILL NEED TO IDENTIFY WHICH IS THE INTERIOR AND | | | EXTERIOR OF THE BUILDING. DEPENDING | | | ON THE CONFIGURATION 2 OF THE 4 OPENINGS WILL BE | | | LOCATED WITHIN A ZONE 5 OR END ZONE WITH NEGATIVE | | | PRESSURES WHICH WILL BE HIGHER IN VALUE. | | | FBC-B 1609.1.1/ ASCE 7-05. | | | | | | 2) THE CONTRACTOR HAS SUBMITTED ONLY ONE SET OF FLESHER | | | WINDOW FASTENING SHCEDULE DRAWINGS FWI0094 SHEETS 1-11, | | | 2 SETS WILL BE NEEDED, 1 SET FORTHE FIELD INSPECTOR AND | | | THE SECOND FOR FILE COPY. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|