| Plan Review Notes For Permit 10050374 |
| Permit Number |
10050374 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-06-17 16:26:46 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. ADDRESSED. | | | | | | 2. SHOW ALL REQUIRED FIRE RATED WALLS. IF THE PROPOSED | | | DRYWALL IS A PART OF AN APPROVED ASSEMBLY, PROVIDE | | | SPECIFICATION FOR DRYWALL PROPSED. FBC CHAPTER 7. | | | | | | 2ND REVIEW, PLAN SHOWS DRYWALL REPAIR AT TENANT | | | SEPARATION WALLS AND IN THE CORRIDOR. SHOW ALL FIRE | | | RATED WALLS AND PROPOSED REPAIR, EITHER TESTED ASSEMBLY | | | OR CALCULATED FIRE RESISTANCE, FBC7. FBC708.1(7). | | | | | | 3. ADDRESSED. | | | | | | | | | | | | |
|