Plan Review Notes
Plan Review Notes For Permit 10050374
Permit Number 10050374
Review Stop B
Sequence Number 2
Notes
Date Text
2010-06-17 16:26:46****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. ADDRESSED.
  
 2. SHOW ALL REQUIRED FIRE RATED WALLS. IF THE PROPOSED
 DRYWALL IS A PART OF AN APPROVED ASSEMBLY, PROVIDE
 SPECIFICATION FOR DRYWALL PROPSED. FBC CHAPTER 7.
  
 2ND REVIEW, PLAN SHOWS DRYWALL REPAIR AT TENANT
 SEPARATION WALLS AND IN THE CORRIDOR. SHOW ALL FIRE
 RATED WALLS AND PROPOSED REPAIR, EITHER TESTED ASSEMBLY
 OR CALCULATED FIRE RESISTANCE, FBC7. FBC708.1(7).
  
 3. ADDRESSED.
  
  
  
  