| Plan Review Notes For Permit 10050369 |
| Permit Number |
10050369 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-09 08:33:07 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. FBC R302.1, SEE TABLE R302.1 REGARDING PROJECTIONS, | | | WALLS, AND DISTANCE TO THE PROPERTY LINE. A SOLID ROOF | | | IS PROPOSED SUPPORTED BY A WALL AT THE PROPERTY LINE; | | | THIS DOES NOT COMPLY WITH THE REQUIREMENTS OF FBC R302. | | | | | | 2. PROVIDE THE DIMENSION OF THE WIDTH OF THE WALL, SHOW | | | THE WIDTH OF THE WALL LOCATED ON THIS PARCEL, AND SHOW | | | HOW THIS IMPROVEMENT (DETAIL SHOWING THAT THE | | | ATTACHMENT OF THE PROPOSED SCREEN ENCLOSURE TO THE | | | WALL) WILL NOT ENCROACH THE PROPERTY LINE. | | | | | | 3. IT APPEARS THAT THE PROPOSED IMPROVEMENT WILL DRAIN | | | ONTO THE ADJACENT PROPERTY, SEE FBC R401.3 AND REVISE | | | PLAN TO COMPLIANCE. | | | | | | |
|