| Plan Review Notes For Permit 10050327 |
| Permit Number |
10050327 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-18 17:01:39 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE | | | ACCORDION SHUTTERS AS REQUIRED BY FAC RULE 9B-72. | | | | | | 2) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE ACCORDION SHUTTERS. SPECIFY THE MOUNT, | | | FASTENER TYPE AND SPACING, SPANS, ETC. FBC R301.1 | | | | | | 3) SUBMIT 2 COPIES OF A FLOOR PLAN INDICATING THE | | | LOCATION, TYPE AND SIZE OF THE WINDOWS AND DOORS THAT | | | WILL BE REPLACED. FBC 301.1 | | | | | | 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | EXTERIOR DOOR IS EXPIRED. SUBMIT CURRENT PRODUCT | | | APPROVALS. RULE 9B-72 | | | | | | 5) PRODUCT APPROVALS WERE SUBMITTED FOR WINDOW | | | MULLIONS. PLEASE SPECIFY THE WHICH WINDOWS WILL BE | | | MULLED TOGETHER. SPECIFY THE SIZES AND CONFIGURATION. | | | FBC R301.1 | | | | | | 6) PRODUCT APPROVALS WERE SUBMITTED FOR IMPACT RATED | | | WINDOWS, HOWEVER, THE SCOPE OF WORK SPECIFIES WINDOWS | | | WITH ACCORDION SHUTTERS. PLEASE CLARIFY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|