| 2010-06-03 13:40:25 | *****DENIED REVISION***** | | | | | | 1) SPRINKLERS PROTECTING SMALL COMPARTMENTS CANNOT BE | | | OMMITTED FROM THE HYDRAULIC CALCULATION WHEN THE REMOTE | | | AREA IS ALREADY REDUCED IN SIZE FROM 1,500 SQ.FT. TO | | | 900 SQ.FT. WITH THE USE OF QUICK RESPONSE SPRINKLERS | | | (NFPA 13, SECTION 14.4.4.4.2). THIS AFFECTS PROOF | | | CALCULATION #2 AND #3. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 | | | 561-804-4700 | | | | | | | | | |
|