2010-06-03 13:40:25*****DENIED REVISION*****
  
 1) SPRINKLERS PROTECTING SMALL COMPARTMENTS CANNOT BE
 OMMITTED FROM THE HYDRAULIC CALCULATION WHEN THE REMOTE
 AREA IS ALREADY REDUCED IN SIZE FROM 1,500 SQ.FT. TO
 900 SQ.FT. WITH THE USE OF QUICK RESPONSE SPRINKLERS
 (NFPA 13, SECTION 14.4.4.4.2). THIS AFFECTS PROOF
 CALCULATION #2 AND #3.
  
  
 CAPT. MICHAEL A. WILLIAMS
 & WESLEY JOLIN
 FIRE PLAN REVIEW