| Plan Review Notes For Permit 10050317 |
| Permit Number |
10050317 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-19 19:05:00 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE PROVIDE TWO COMPLETE SETS OF THE INSTALLATION | | | SCHEDULE. | | | | | | 2. SEE INSTALLATION SCHEDULE. 1.5" EDGE DISTANCE | | | REQUIRES A .35 FACTOR, SEE PAGE 11. PLEASE REVISE | | | ANCHOR SPACING. | | | | | | 3. ON THE INSTALLATION SCHEDULE, THE COLUMN SHUTTER | | | MOUNTING CONNECTION TYPE SHOULD SPECIFY WHICH | | | CONNECTION TYPE IS PROPOSED. THIS APPEARS TO BE FLOOR | | | MOUNTING 7, WALL MOUNTING 1, AND WALL MOUNTING 3 (BASED | | | ON HIGHLIGHTED PRODUCT APPROVAL). PLEASE INCORPORATE | | | THIS INFORMATION INTO THE INSTALLATION SCHEDULE, WHICH | | | IS OPENING SPECIFIC. | | | | | | |
|