Plan Review Notes
Plan Review Notes For Permit 10050311
Permit Number 10050311
Review Stop B
Sequence Number 1
Notes
Date Text
2010-05-20 09:37:46BUILDING PLAN REVIEW
 PERMIT: 10010055 / REV: 10050311
 ADD: 1601 FORUM PLACE #500
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DESIGN PROFESSIONAL: ALLEN BURST
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). A REVISION WILL BE
 REQUIRED, ADDTIONAL REVIEWS WITH ASSOCIATED FEES WILL
 BE REQUIRED.
  
 I SPOKE WITH MR. BURST IN REGAURDS TO THE OCCUPANT LOAD
 BEING 61 REQUIRING:
  
 1) 2 EXITS A THIRD THE DISTANCE APART, FBC 1015.2.1,
 EXCEPTION #2.
 2) THE SECOND ISSUE THESE TWO SINGLE EXIT DOORS WILL
 NEED TO SWING IN THE DIRECTION OF THE EGRESS TRAVEL FBC
 1008.1.2.
 3) THE THIRD ISSUE IS THE TWO SINGLE EXIT DOORS WILL
 BOTH REQUIRE EXIT SIGNAGE SEE E-2 ONE SIGN IS MISSING.
  
 JIM WITMER C. B. O.