| Plan Review Notes For Permit 10050267 |
| Permit Number |
10050267 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-02 17:03:23 | 2007 FBC W/2009 REVISIONS | | | ADDITION | | | | | | DENIED BY PLUMBING | | | | | | 1) THE 2" HORIZONTAL DRY VENT FOR THE WATER CLOSET | | | SHOWN ON THE SANITARY ISOMETRIC ON SHEET 14 IS NOT | | | ALLOWED. FBC R P3104.4 REQUIRES EVERY DRY VENT TO RISE | | | VERTICALLY TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL OF | | | THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. | | | | | | 2) FBC R P3005.2.6 REQUIRES AN ACCESSIBLE CLEANOUT AT | | | THE BASE OF EACH VERTICAL WASTE OR SOIL STACK. SHOW | | | CLEANOUT AT BASE OF SOIL STACK FROM THE SECOND FLOOR ON | | | ISOMETRIC. | | | | | | 3) THE WATER ISOMETRIC GOES FROM 3/4" TO 1" TO 3/4" ON | | | THE HOT WATER JUST PAST THE TANKLESS HEATER. THIS | | | APPEARS TO BE AN ERROR. PLEASE REVIEW. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|