| 2010-06-03 14:01:04 | 2007 FBC W/2009 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ALTHOUGH THE PLANS HAVE BEEN REVIEWED AND STAMPED |
| | FOR IMPACT FEES BY PALM BEACH COUNTY, TWO COPIES OF THE |
| | PAID RECEIPT FROM PBC ARE REQUIRED TO BE SUBMITTED. |
| | |
| | 2) THE PROJECT IS LOCATED IN AN A5 FLOOD ZONE WITH A |
| | BASE FLOOD ELEVATION OF 7 FT. THE CITY OF WEST PALM |
| | BEACH CITY CODE ARTICLE XVII SECTION 94-546 REQUIRES |
| | ALL NEW RESIDENTIAL CONSTRUCTION OR SUBSTANTIAL |
| | IMPROVEMENT OF ANY EXISTING RESIDENTIAL STRUCTURE TO |
| | HAVE THE LOWEST FLOOR ELEVATED TO SIX INCHES ABOVE THE |
| | BASE FLOOD ELEVATION. THE SURVEY THAT WAS SUBMITTED |
| | INDICATES THE EXISTING STRUCTURE HAS A FINISHED FLOOR |
| | ELEVATION OF 6.87 FT. THIS PROJECT WILL REQUIRE THAT |
| | THE EXISTING STRUCTURE AND THE LOWEST FLOOR OF THE |
| | ADDITION AS WELL AS THE EQUIPMENT SERVICING THE |
| | BUILDING BE ELEVATED TO A MINIMUM OF 7.6 FT. ABOVE BFE. |
| | PROVIDE PLANS SHOWING COMPLIANCE. |
| | |
| | 3) SUBMIT TWO SETS OF SITE DRAINAGE PLANS SHOWING |
| | COMPLIANCE WITH FBC R401.3 . |
| | |
| | 4) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE |
| | INLAND WATERWAY. BASED ON FBC R301.2.1.4.3 THE EXPOSURE |
| | CATEGORY IS C AND THE ROOF SHEATHING UPLIFT AND |
| | ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED BY 20 |
| | PERCENT. PLEASE CORRECT PLANS. |
| | |
| | 5) THE ENERGY CALCULATIONS AND PLANS DO NOT MATCH. THE |
| | EXTERIOR WALL R-VALUES DIFFER. THE CEILING TYPE ON THE |
| | FORM IS VENTED ATTIC AND THE PLANS HAVE AN UN-VENTED |
| | ATTIC WITH ICYNENE. ITEM #1 ON THE FORM SHOULD BE NEW |
| | ADDITION, NOT EXISTING. THE OWNER AGENT IS REQUIRED TO |
| | SIGN THE FORM. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R310.1 FOR EMERGENCY ESCAPE |
| | AND RESCUE OPENING AT THE GUEST ROOM /OFFICE. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR |
| | SMOKE ALARMS AND CARBON MONOXIDE DETECTORS. |
| | |
| | 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR THE STRUCTURAL WINDOW MULLIONS. |
| | |
| | 9) SUBMIT LEGIBLE DRAWINGS FOR THE RAYNOR SECTIONAL |
| | GARAGE DOOR PRODUCT APPROVALS. |
| | |