| Plan Review Notes For Permit 10050262 |
| Permit Number |
10050262 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-14 13:53:11 | *****REVISION DENIED***** | | | | | | | | | | | | 1) ORIGINAL HYDRAULIC CALCULATIONS SUBMITTED WERE FOR | | | ORDINARY HAZARD GROUP II. NEW HYDRAULIC CALCULATIONS | | | SUBMITTED WERE FOR LIGHT HAZARD. PLEASE EXPLAIN. | | | | | | 2) STANDARD SPRAY SPRINKLERS SPACED 6 FEET APART TO WET | | | SURFACE OF GLASS STOREFRONT CURTAINWALL (SUBSTITUTION | | | FOR 1-HR RATED BARRIER) IS NOT PERMITTED. THIS | | | EQUIVALENCY | | | APPLIES TO ATRIUM SEPARATIONS. CONSIDER USE OF SPECIFIC | | | APPLICATION WINDOW SPRINKLERS FOR EACH SECTION OF | | | GLAZING. WINDOW SPRINKLER DEMAND WOULD NEED | | | TO BE ADDED TO THE HYDRAULIC CALCULATIONS. | | | | | | 3) GLASS DOOR CANNOT BE PROTECTED WITH SPRINKLERS. FIRE | | | RATED DOORS ARE REQUIRED. | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|