Plan Review Notes
Plan Review Notes For Permit 10050262
Permit Number 10050262
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-05-14 13:53:11*****REVISION DENIED*****
  
  
  
 1) ORIGINAL HYDRAULIC CALCULATIONS SUBMITTED WERE FOR
 ORDINARY HAZARD GROUP II. NEW HYDRAULIC CALCULATIONS
 SUBMITTED WERE FOR LIGHT HAZARD. PLEASE EXPLAIN.
  
 2) STANDARD SPRAY SPRINKLERS SPACED 6 FEET APART TO WET
 SURFACE OF GLASS STOREFRONT CURTAINWALL (SUBSTITUTION
 FOR 1-HR RATED BARRIER) IS NOT PERMITTED. THIS
 EQUIVALENCY
 APPLIES TO ATRIUM SEPARATIONS. CONSIDER USE OF SPECIFIC
 APPLICATION WINDOW SPRINKLERS FOR EACH SECTION OF
 GLAZING. WINDOW SPRINKLER DEMAND WOULD NEED
 TO BE ADDED TO THE HYDRAULIC CALCULATIONS.
  
 3) GLASS DOOR CANNOT BE PROTECTED WITH SPRINKLERS. FIRE
 RATED DOORS ARE REQUIRED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW