| Plan Review Notes For Permit 10050225 |
| Permit Number |
10050225 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-13 13:21:09 | REVIEW #1 | | | FAILED | | | | | | 210.70 (A) (3) STORAGE OR EQUIPMENT SPACES. FOR ATTICS, | | | UNDERFLOOR SPACES, UTILITY ROOMS, AND BASEMENTS, AT | | | LEAST ONE LIGHTING OUTLET CONTAINING A SWITCH OR | | | CONTROLLED BY A WALL SWITCH SHALL BE INSTALLED WHERE | | | THESE SPACES ARE USED FOR STORAGE OR CONTAIN EQUIPMENT | | | REQUIRING SERVICING. AT LEAST ONE POINT OF CONTROL | | | SHALL BE AT THE USUAL POINT OF ENTRY TO THESE SPACES. | | | THE LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE | | | EQUIPMENT REQUIRING SERVICING.***SUBMIT A FLOOR PLAN | | | LOCATING THE REQUIRED OUTLETS PER THIS ARTICLE. | | | | | | PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|