| 2010-05-10 16:51:01 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PLEASE PROVIDE TWO IDENTICAL SETS OF DOCUMENTS FOR |
| | PERMIT ISSUANCE. |
| | |
| | 2. THE DOCUMENT TITLED "PRODUCT APPROVAL REVIEW FORM" |
| | SHOWS THAT THE NOA LIMIT IS -60PSF. I AM UNABLE TO |
| | LOCATE THIS ON THE NOA, WAS THE CORRECT PRODUCT |
| | APPROVAL PROVIDED? SEE OTHER COMMENTS, ALL OPENINGS MAY |
| | NOT MEET REQUIRED DESIGN PRESSURES. |
| | |
| | 3. PLEASE HAVE THE ENGINEER DETERMINE ZONE FOR OPENING |
| | 2, CORNER UNITS, OR USE ZONE 5 PRESSURES. THE KITCHEN |
| | WINDOW IS A SMALL WINDOW WHICH, BASED ON THE FLOOR PLAN |
| | AND PHOTOGRAPHS, SHOULD BE IN ZONE 5. SEE ENGINEERING, |
| | INSTRUCTIONS #8. |
| | |
| | 4. PLEASE EXPLAIN HOW YOU HAVE DETERMINED SQUARE FOOT |
| | AREAS. FOR INSTANCE: APT 101, OPENING 1, 48X72, IS A |
| | 24SF OPENING, BUT 35SF PRESSURES WERE USED. SEE OTHER |
| | COMMENTS REGARDING ZONE AND BUILDING HEIGHT; -58.8 PSF |
| | USED, BUT -113.7PSF MAY BE REQUIRED. |
| | |
| | 5. PLEASE EXPLAIN HOW YOU HAVE DETERMINED THE BUILDING |
| | HEIGHT. 70' WAS USED ON THE DESIGN PRESSURE CHART, BUT |
| | THIS BUILDING APPEARS TO BE 9 STORIES. TYPICALLY A |
| | MINIMUM OF 10FT PER STORY IS USED TO ESTIMATE BUILDING |
| | HEIGHT, WHICH RESULTS IN 7.7' PER STORY. EITHER USE 90' |
| | AS BUILDING HEIGHT OR HAVE THE ENGINEER CERTIFY |
| | BUILDING HEIGHT. |
| | |
| | |
| | |