Plan Review Notes
Plan Review Notes For Permit 10050103
Permit Number 10050103
Review Stop B
Sequence Number 1
Notes
Date Text
2010-05-05 08:58:42RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- BUILDING HAS A VALUATION OF MORE THAN $300,000. NEED
 TO PROVIDE COMPLIANCE WITH THE ROOF TO WALL CONNECTION
 IMPROVEMENTS AS REQUIRED BY SEC. 611.8 OF 2007 FLORIDA
 BUILDING CODE-EXISTING BUILDING.
  
 2- PROVIDE PRODUCT APPROVAL FOR POLYFOAM TO BE USED AS
 REQUIRED BY DCA RULE 9B -72.
  
 ***NOTE: TILE BOND ADHESIVE CAN'T BE USED BECAUSE IT
 DOESN'T MEET THE DESIGN PRESSURES FOR THIS BUILDING.
 THIS BUILDING IS LOCATED ON EXPOSURE "C" AND THE DESIGN
 PRESSRUES ARE HIGHER THAN 26.1. SEE ROOF TILE PRODUCT
 APPROVAL AND PROVIDE ANOTHER LISTED ADHESIVE THAT MEETS
 THE DESIGN PRESSURES FOR THIS BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT VALUATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. OWES $123.65
 FOR UPDATED VALUATION.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION BUILDING PLANS EXAMINER
 (561)805-6712.
  