2010-05-10 14:55:45TEST AND BALANCE REPORT DENIED
 1) AIR HANDLER UNITS MUST BE +/- 10 % WITH ALL
 DIFFUSERS AND DAMPERS OPEN .
 2) AHU # 4 , THE REVISED PLAN SHOWS THE FRESH AIR AS 12
 IN. REMOVE THE 8 IN. FRESH AIR AND INSTALL THE 12 IN.
 AS PER PLAN.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732