Plan Review Notes
Plan Review Notes For Permit 10040776
Permit Number 10040776
Review Stop B
Sequence Number 1
Notes
Date Text
2010-05-20 12:05:492007 FBC W/2009 REVISIONS
  
 1) SHEET 1 OF THE CARPORT ENCLOSURE SPECIFIES THAT IT
 IS EXPOSURE CATEGORY B. BECAUSE THE STRUCTURE IS
 LOCATED WITHIN 1500 FT OF THE INTRACOASTAL WATERWAY, IT
 IS EXPOSURE CATEGORY C. PLEASE CORRECT.
  
 2) FBC R704.1 REQUIRES CLEARANCE BETWEEN WALL COVERINGS
 AND FINAL EARTH GRADE TO BE A MINIMUM OF 6" FOR TERMITE
 INSPECTION. ALSO SEE R404.1.6 HEIGHT ABOVE FINISH
 GRADE.
  
 3) ASTM C 1063 REQUIRES FOUNDATION WEEP SCREEDS AT THE
 BOTTOM OF FRAMED EXTERIOR WALLS.
  
 4) SHOW COMPLIANCE WITH FBC R 303.3 FOR BATHROOM
 VENTILATION AFTER THE WINDOW IS ENCLOSED.
  
 5) FBC R 309.1 DOES NOT PERMIT OPENINGS FROM THE GARAGE
 TO SLEEPING ROOMS. SHOW COMPLIANCE.
  
 6) FBC R 309.2 REQUIRES THE GARAGE TO BE SEPARATED FROM
 THE RESIDENCE AND ITS ATTIC AREA BY NOT LESS THAN 1/2"
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. SHOW
 COMPLIANCE.
  
 7) THE DOOR FROM THE GARAGE TO THE RESIDENCE IS
 REQUIRED TO COMPLY WITH FBC R 309.2. SPECIFY DOOR TYPE
 ON PLANS.
  
 8) SPECIFY THE REQUIRED OPENING PRESSURES FOR THE
 EXTERIOR DOORS ON THE PLANS. FBC R 301.2.1
  
 9) THE PRODUCT APPROVAL SUBMITTED FOR THE SECTIONAL
 GARAGE DOOR, NOA 09-0128.01 IS MISSING PARTS OF THE
 DRAWINGS. IT APPEARS THAT THE DRAWING DID NOT FIT THE
 PAGE WHEN IT WAS DOWNLOADED. PLEASE CORRECT.
  
 10) SHOW COMPLIANCE WITH FBC R 313.2.1 FOR SMOKE ALARMS
 AND R 313.4 FOR CARBON MONOXIDE PROTECTION.
  
 11) PROVIDE DOOR BUCK DETAILS FOR THE OVERHEAD GARAGE
 DOOR ON THE PLANS. SEE SHEET 4 OF DRAWING 98-05 FOR NOA
 09-0128.01 AND FBC R 613.6.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]