| Plan Review Notes For Permit 10040770 |
| Permit Number |
10040770 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-06-07 10:43:11 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | (NEW NOA AND CALCULATIONS SUBMITTED) | | | | | | 1. PLEASE SEE THE RAS117 CALCULATIONS, SHEET 1. ZONE 2 | | | STATES THAT SPACING WILL BE: | | | | | | 9.3"O.C. FOR ROWS 12" APART (3 ROWS) | | | | | | PLEASE EXPLAIN; FOUR ROWS TOTAL (3 FIELD ROWS, 1 LAP | | | ROW) PLUS A 4" LAP WOULD EQUAL A 52" SHEET, BUT THE | | | BASE SHEET WIDTH IS 39.37". | | | | | | 2. CALCULATIONS STATE THAT THE SF/FASTENER IS 1.02'; | | | PLEASE EXPLAIN HOW THIS NUMBER HAS BEEN DERIVED AS I | | | BELIEVE THIS SHOULD BE .88'. | | | | | | 3. FASTENING PATTERN IS NOT CLEAR. THE APPROVED | | | ASSEMBLY INCLUDES A 9" LAP ROW, TWO 12" FIELD ROWS. FOR | | | ZONES 2 AND 3, LAP ROW WAS NOT SPECIFIED. IS IT THE | | | INTENT TO HAVE THE LAP ROWS AT 9" OR 12"? WITHOUT THIS | | | INFORMATION, COMPLIANCE WITH RAS117 CANNOT BE | | | DETERMINED. | | | | | | 4. SEE RAS117, SPACING IS TO BE ROUNDED DOWN TO THE | | | NEAREST INCH. | | | | | | PLEASE CONTACT ME TO DISCUSS A PROVISO FOR THIS PERMIT. | | | | | | | | | | | | | | | | | | |
|